Atlas tool estimate
Inverter DC current calculator
An inverter turns battery power into mains-style AC. Compare the estimated battery and AC currents for a steady load by typing your own figures. For cable and fuse sizes, follow the inverter manual.
Route card
Enter a load, a battery voltage, an efficiency and an AC voltage to see the estimate.
- Battery-side (DC) current
- 0 A
- AC-side current
- 0 A
- Power taken from the battery
- 0 W
- DC current ÷ AC current
- 0 ×
How the estimate is worked out
DC current IDC = P ÷ (Vbattery × η)
AC current IAC = P ÷ VAC
Battery power Pbattery = P ÷ η
DC ÷ AC ratio IDC ÷ IAC = VAC ÷ (Vbattery × η)
P is the AC output power in watts. VAC and IAC are RMS values, the usual way AC voltage and current are quoted. η (eta) is the inverter efficiency written as a fraction, so 90 % is 0.90, and for the battery-only case it is defined as AC output power ÷ DC input power. Power is voltage times current (P = V × I), so current is power divided by voltage. The inverter must also cover its own losses, which is why the load is divided by the efficiency first. The ratio line follows from the first two: the load P cancels, and at a power factor of 1 the ratio depends only on the AC voltage, the battery voltage and the efficiency. Depending on those figures, the AC current can be the higher of the two.
Assumptions
- The load is real power in watts, not VA.
- The AC current assumes a power factor of 1, as for a kettle, heater or other resistive load. Loads with a lower power factor, such as many motors, draw more AC current for the same watts.
- The battery is taken at the voltage you enter. Enter the DC voltage expected under load. For the same watts and efficiency, a lower DC voltage gives a higher current.
- The efficiency is a single figure. If the datasheet gives the inverter's rated RMS output and its efficiency at your load, use that figure; peak efficiency can differ from efficiency at the load, and a lower efficiency raises the DC current.
- The 12, 24 and 48 V DC and 120 and 230 V AC buttons are example presets. Other voltages can be typed in, within the calculator limits: load 1 to 1,000,000 W, battery and AC voltage 1 to 1,000 V, efficiency 10 to 100 %. Those limits keep the results finite; they are not product limits.
- Not included: start-up surge, the inverter's own no-load draw, and cable or fuse losses.
- Every result is an estimate. For cable and fuse sizes, follow the inverter manual and its rated currents.
Sources
- The International System of Units (SI Brochure), 9th edition, Bureau International des Poids et Mesures (BIPM). The definitions of the watt and the volt (one volt is one watt per ampere) are in Table 4 of the brochure.
- SI Units – Electric Current, National Institute of Standards and Technology (NIST). States the same relationship, 1 V = 1 W/A.
- University Physics Volume 2, section 9.5 Electrical Energy and Power, OpenStax. Electric power as P = IV.
- University Physics Volume 2, section 15.4 Power in an AC Circuit, OpenStax. RMS power and the resistive load at unity power factor.
- CEC Inverter Test Protocol, PV Performance Modeling Collaborative, Sandia National Laboratories. Inverter efficiency as the ratio of AC output power to DC input power.
- MultiPlus-II 120 V, technical specifications and MultiPlus-II 230 V, technical specifications, Victron Energy. Cited only as examples of the 12, 24 and 48 V DC and 120 and 230 V AC voltages used in the presets; this calculator does not use their product figures.